All the main things - in a small format
Unique addressable interface
- addressable devices
- length
- reaction time
- maximum resistance
- radial branches

Important elements of the board

Also, if you need to expand the system or complicate the topology, you can add an addressable interface using M-LOOP in the universal slot of the control panel.
Fire protection automation
There are two built-in relay outputs in Tiras PRIME A mini with the ability to work with communication line control.
No additional devices are required to control devices that require relay outputs (e.g., voice notification systems).
1. M-OUT2R box – connects via RS-485 interface and adds two relay outputs to the system. Switching current up to 10 A.
2. M-OUT8R – connects via RS-485 interface or to an addressable ring using AM-Converter. Adds 8 relay outputs to the system with a switching current of up to 5 A.
3. AM-OUT1R+ – addressable relay module with one relay output and two universal inputs.
Does not require an external power supply, as it is equipped with a bistable relay. In addition to one powerful relay (15 A closing, 5 A opening), the module is equipped with two universal inputs for fire alarm control and a 220 V control input.
4. AM-OUT2R – connects to an addressable ring and adds two bistable relays to the system. Does not require an external power supply. Switching current up to 10 A.
5. AM-IN4. Addressable input module. The module is equipped with four universal inputs for controlling fire protection automation: elevators, smoke extraction systems, smoke dampers, water pumps, etc.
There are many application options, both in combination with relay modules and independently.
Scripts
Each script has up to 8 activation criteria, to which different logic can be applied (when all criteria are met or at least one (AND/OR)), and up to 16 actions.

LiFePO4 support
Batteries of this type charge faster and are less vulnerable to unstable power supply than classic lead-acid batteries.

New communicator

Configuration
TRS-Monitor - IN DEVELOPMENT
Additional features
Technical features
Maximum in the system: 2
loop or radial
up to 250 in the loop, up to 32 in the radial
24 V
125 ohms
up to 2000 m
from any device
Maximum in the system: 128
(installation on the CP board)
220 V, 50 Hz
lead-acid or LiFePO4 battery 7-9 A*h
35 W
400 mА
280×280×80 mm
1.25 kg
IP30
from -10 to +40°C