address
Ukraine, Vinnytsia, 2nd Lane Khmelnytske shosse 8
MBI-2

MBI-2

MBI-2 - intrinsically safe barrier module is used to make detectors or sounder wiring safe in explosive areas

Purpose

MBI-2 - intrinsically safe barrier module is used to make detectors or sounder wiring safe in explosive areas and has marking "Ex II (2) G [Ex ib Gb] IIC" (for MBI-2) and "Ex II (2) G [Ex ib Gb] IIB" (for MBI-2(24V)).
2 models: MBI-2 and MBI-2(24V) - for connection to FCP wiring with operating voltage 12V or 24V respectively.
Devices can be connected to intrinsically safe lines:
- fire detectors SPD-2 «Tiras» Ex, SPT «Tiras» Ex and MCP SPR «Tiras» Ex;
- light signs OS Ex, light and sound sirens OSZ Ex;
- emergency abort devices EAD «Tiras» Ex and manual release devices MRD «Tiras» Ex.

    Technical parameters

    Intrinsically safe circuit parameters for MBI-2/MBI-2(24V)
    Max. voltage:
    19/31.5V
    Max. output current:
    130/210 mA
    Max. output inductance:
    1 mH
    Max. output capacity:
    0,1/0.48 μF
    Resistance:
    174 Ohm
    Enclosure
    Dimensions:
    93х75х35 mm
    Weight:
    110 g
    Enclosure protection degree:
    ІР20
    Operating temperature range:
    from -10°C to+40°C