Unique addressable interface
- addressable devices
- length
- reaction time
- maximum resistance
- separate controller for each addressable device
- radial branches
- load mode selection
- special operation mode "System Bus"

Important elements of the board

Improved user interface
Hierarchical system
Each FPC is configured separately, then the FPCs are networked and each of them can display information both on its own subsystem and on all other subsystems (other FPCs) if the “Display events of all FPCs” option is enabled for it.
SPE technology allows distances of up to 700 m to be achieved using standard shielded twisted pair cable, and up to 1700 m using specialized cable.
The built-in Ethernet interface can be used as a communicator.
Fire protection automation
We converted four transistor outputs from HW1 into two transistor and two relay outputs. At the same time, both outputs retain the ability to work with communication line control.
Now, no additional devices are needed to control devices that require relay outputs.
To implement one direction of fire extinguishing, you need to use the TIRAS 1X control panel, which is connected to the addressable ring using the AM-Converter module.
To implement relay outputs for starting automation devices in the Tiras PRIME A fire alarm control panel, the following options are used: AM-OUT2R, M-OUT8R, and AM-OUT1R+ modules.
1. AM-OUT2R – connects to the addressable loop and adds two relay outputs to the system. Switching current up to 10 A.
2. M-OUT8R – connects to the address ring using AM-Converter. This connection adds 8 relay outputs with a switching current of up to 5 A to the system.
3. AM-OUT1R+ – addressable relay module with one relay output and two universal inputs.
The main advantage and difference from AM-OUT2R is that it does not require an external power supply, as it is equipped with a bistable relay. In addition to one powerful relay (15 A for closing, 5 A for opening), the module is equipped with two universal inputs for controlling fire protection automation and a 220 V control input.
AM-IN4. Addressable input module. The module is equipped with four universal inputs for controlling fire protection automation: dampers, elevators, smoke removal, pumps, etc.
There are many application options, both in combination with relay modules and independently.
For cases where dozens of input/output modules connected by dozens of automation scenarios are connected to the address interface, the speed of exchange in the address interface is very important to us.
Especially for such cases, we have developed a special operating mode for the address interface called “system bus.” Enabling this mode increases the speed of exchange in the address interface by 4 times and allows complex logical automation connections to be processed significantly faster.
Scripts
Each script has up to 8 activation conditions to which different logic can be applied - when all conditions are met or at least one (AND/OR) - and up to 16 actions.

LiFePO4 support
Batteries of this type charge faster and are less vulnerable to unstable power supply than classic lead-acid batteries.

New communicator

P-IND PRIME A
P-IND PRIME A connects to the control panel via the SPE interface, so it can be placed at a considerable distance (up to 1700 meters) from the control panel.
The maximum number of P-IND PRIME A devices in the system is 4.
TRS-Monitor - IN DEVELOPMENT
Additional features
Technical features
Maximum in the system: 128
loop or radial
up to 250 in the loop, up to 32 in the radial
24 V
125 ohms
up to 2000 m
from any device
Maximum in the system: 1000
Maximum in the system: 1000
(installation on the CP board)
220 V, 50 Hz
2 lead-acid or LiFePO4 batteries 7-9 A*h
50 W
1 A
350x365x100 mm
3 kg
IP30
from -10 to +40°C